Cable HS XKDCu(Al)T 500 mm² Cu 150 kV
Cable HS XKDCu(Al)T 500 mm² Cu 150 kV
HV XLPE insulated single core cables with a copper wire screen, longitudinal and radial watertightness.
Read more- Nexans ref. : XKDCu(Al)T 500 Cu 150 kV
Description
Description
Standards
-
TestIEC 60840; IEC 62067
-
NationalHD 632 Section O
Applications
- Underground distribution networks
- Pipe laying and ground laying
- Installation in electrical substations
These products are manufactured according to your specifications. Therefore, there is no standard product list. For more information, please contact us.
Construction
- Copper or aluminum conductor
- Extruded inner semi-conductor
- Cross-linked PE insulation (XLPE)
- Extruded outer semi-conductor
- Semi-conductive swelling tape
- Metal shielding
- Semi-conductive swelling tape
- Radial sealing (copper or aluminum tape)
- Outer HDPE sheath
Properties
- Longitudinal and radial sealing provided by two layers of tapes that swell in the presence of moisture and prevent the spread of water in case of injury to the sheath
- Special abrasion resistant PE outer jacket with low shrinkage rate
- Cross-linked PE insulation (XLPE) with high dielectric strength and low losses
- Halogen free
Characteristics
Characteristics
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
500 mm²
Conductor diameter
26.5 mm
Diameter over insulation
65.3 mm
Outer Diameter
78.7 mm
Screen section
95 mm²
Approximate weight
9.3 kg/m
Electrical characteristics
Electrical characteristics
Operating voltage
150 kV
Permissible short circuit current screen 1s
15.0 kA
Permissible short circuit current conductor 1s
71 kA
Max. DC resistance of the conductor at 20°C
0.037 Ohm/km
Capacity core to screen
0.173 pF/m
I max. @ 90°C-buried in trefoil joined
795 A
I max. @ 90°C-buried in trefoil spaced
825 A
I max. @ 90°C-buried in flat formation joined
750 A
I max. @ 90°C-buried in flat formation spaced
820 A
I max. @ 75°C-buried in trefoil joined
715 A
I max. @ 75°C-buried in trefoil spaced
740 A
I max. @ 75°C-buried in flat formation joined
675 A
I max. @ 75°C-buried in flat formation spaced
735 A
Load factor
1
Sheaths grounding
1 point
Thermal soil resistivity dry zone
0.85 °K.m/W
Mechanical characteristics
Mechanical characteristics
Maximum tensile load during service (Tl)
3000.0 daN
Usage characteristics
Usage characteristics
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient ground temperature
20 °C
Laying operation bending radius
2800 mm
Laying depth, center of system
1000 mm
Laying tube diameter
120 mm
Distance between tubes (X)
200 mm
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania